SG

ABOUT PRODUCT

Feature

Fast closing, Fast opening or slow opening or adjustable opening, Fitted with flow adjustment device, Gas safety valve group ‘A’ in accordance with DN 3391/3, Internationally approved designs, Large flow rate, Long life design, Low pressure loss through valve., Operating pressures 0 to 200 mbar, 0 to 360 mbar, Robust, maintenance free, leakage free construction

Operating Temperature

(-)20° to (+)60°C

Closing Time

Less than 1 second

Coil Protection

IP-54 according to IS-2147

Coil Insulation

Class “F”

Power consumption

Will be in accordance with specification table. Power consumption does not change during pick-up and holding operation.

Cable Gland

pg11 for size 15 to 25NB, Pg 13.5 for size 40 to 100NB

Application

For protection, regulation and control of air and gas supply to gas burner/gas devices.

Valve Body

For protection, regulation and control of air and gas supply to gas burner/gas devices.

Seat

Buna Nitrile, on special request ‘Viton’

Magnetic Construction

430F

Operating Pressure

Refer to the specification table

Opening Time

SG..N without damping unit, fast opening – 0.5 Sec. SG..L with damping unit, slow opening approx.10 Sec.

Switching Frequency

Arbitrary

Power factor

1

Standard Voltage

110/220/240V +10%/-5%, 50Hz; 24V+10%/–15. Coils on AC voltage (24 VAC excluded) are fed through protective circuit and rectifier. For 24V AC external protective circuit with rectifier must be provided. For 24V DC external protective circuit must be provided.

Duty Cycle

100%

Fuse

Max. 6.3 Amperes with anti surge protection

Fluids

All gases in accordance with DVGW code of practice G260/1 Natural gas, LPG, Methane, Bio-gas special construction required , air or any other inert gas.

Technical Data

SG.pdf

Diagrams

RELATED PRODUCTS