SGZ

ABOUT PRODUCT

Feature

Robust & long life construction,, Suitable for maximum pressure 360 millibar, Two stage operation with lower firing rate

End Connection

Screwed to BSP/NPT (F) Or Flanged to ANSI B16.5 Class 150 RF

Pressure Test Points

1/4” NPT on inlet and outlet of the valve

Cable Gland

Pg11 (upto 40mm size), & Pg 13.5 (from 50-65mm)

Switching Frequency

Universal with full reproducibility of instant passage of gas 5 seconds waiting period between 2 operations.

Fluids

Natural Gas, LPG in gaseous form, Town Gas, Bio-gas etc.

Body

Aluminium Silicon Alloy Castings

Disc Seal

Perbunan

Inbuilt Strainer

Brass (Size 15-40/32mm) Stainless Steel (40-65mm)

Working Temperature

-15°C to +60°C

Working Press

360milibar maximum

Voltage

230 VAC (+10/-15%),50/60 Hz Standard via protective circuit rectifiers

Coil Protection

As per IP-54 (According to IS 2147) Class “F” insulated

Opening Time

0.5 to 5seconds for 1st stage (adjustable) 10 seconds for 2nd stage (fixed)

Closing Time

Less than 1 second, with flow restrictor

Application

A two-step operation is also practical forcapacities < 120kW., For the protection, Shutt-Off and release of the air and gas supply to gas burners and gasdevices with two-step operation., The regulations for heating plant specify a two-step operation for atmospheric boilers with a capacity > 120kW, in order to save energy., The two -step operation allows an improvement of the efficiency at low fire.

Technical Data

SGZ.pdf